Rooftop 4 kN/m 2 and all other floors 4.9 kN/m 2 was applied as a distributed load over the floor area.
Attic Rooftop loads are shown in the image below.
...
Rooftop 2 kN/m 2 and all other floors 2 kN/m 2 was applied as a distributed load over the floor area.
The live load participation rate was determined as 0.3 as per TBDY 2018 Table 4.3. ideCAD Static floor Structural story general settings are set in the HYK LLF section. For detailed information, see:Tekil Düğüm Noktaları Kütleleri Tanımlanması (4.5.9)
...