Along the critical wall height , the ratio of the total vertical reinforcement area in each of the wall end zones is at least 0.002, except for this height, this ratio is not less than 0.001.
|
Tip |
---|
The diameter of the transverse reinforcement to be used in the end regions is not taken less than 8 mm. And the stirrup arms and / or horizontal spacing between crossties, a , greater than the diameter of hoops and crossties 25 of the solid is not selected.
|
...
ICONS
ϕ = Rebar diameter
...
Reinforcement Conditions in Wall End Regions
...
Similarly , an example of a wall drawing created in accordance with TBDY Section 7.6.5 in the upper part of the critical wall height is shown in the picture below.
...