In this example, independent hand calculation results of the internal force values obtained as a result of the earthquake calculation with the mode shapes, periods and mode combination method of a two-storey system with a single span are made and the results of ideCAD Static Structural are compared. The damping ratio used in response spectrum analysis is taken into account as 5%. Full Quadratic Combination (TKB or CQC) has been used as the modal combination method . Independent hand calculation solutions of periods, horizontal displacements and bending moments calculated as a result of modal analysis were made according to Chopra 2012.
...
Info |
---|
Important Note: The masses are defined only on the beam members for ease of independent manual calculation. |
Comparison of periods
Compared Value | ideCAD |
---|
Structural | Manual solution | Percentage of error | |
---|---|---|---|
1st Mode Period | 1.562 | 1.562 | 0% |
2nd Mode Period | 0.5868 | 0.5868 | 0% |
...
Comparison of response displacement results
Node and direction | ideCAD |
---|
Structural | Manual solution | Percentage of error | |
---|---|---|---|
3 DN (UX) | 7.59 | 7.59 | 0% |
1 DN (UX) | 18.8 | 18.8 | 0% |
...
Element end moments comparison (M 33 ) kip-ft
Workman | Node | ideCAD |
---|
Structural | Manual solution | Percentage of error | ||
---|---|---|---|---|
| 3 | 817.99 | 817.99 | 0% |
4 | 817.99 | 817.99 | 0% | |
| one | 433.81 | 433.81 | 0% |
2nd | 433.81 | 433.81 | 0% | |
| 3 | 568.47 | 568.47 | 0% |
5 | 1056.17 | 1056.17 | 0% | |
| one | 433.81 | 433.81 | 0% |
3 | 499.81 | 499.81 | 0% |
...
Geometric Properties and System Description
...
Tip |
---|
T 1 = 1.562 s and T 2 = 0.5868 natural vibration periods results were found to be exactly the same with ideCAD StaticStructural. |
...
After finding the mode shapes and natural vibration periods, the nodal deformation values for each mode must be found.
...
To switch from the horizontal elastic design acceleration spectrum to the displacement spectrum, the following equation is used.
...
Information Annex Appendix-4A Detailed Explanation
Info |
---|
Note: In this example, no carrier system response coefficient will be used. Therefore, R y (µ k , T) = 1 and µ k = 1 will be considered. However, in the Design Based on Strength (DOT) approach, the carrier system behavior coefficient is taken into account. |
...
Tip |
---|
The values of u 1st floor = 7.59 in and u 2nd floor = 18.8 are exactly the same as the results of ideCAD StaticStructural. |
...
Under the influence of an earthquake (for the X direction) element internal forces can be obtained similarly. The building moment diagram can be drawn in the order described below.
...
Elements and end moments are given in the table below when Full Quadratic Joining (TKT or CQC) is applied.
Workman | Node | 1.Mod Moment kip-ft | 2.Mod Moment kip-ft | CQC result kip-ft |
---|---|---|---|---|
| 3 |
|
| 817.99 |
4 |
|
| 817.99 | |
| one |
| 179 | 433.81 |
2nd |
| 179 | 433.81 | |
| 3 | 425 | 374 | 568.47 |
5 | 968 | 412 | 1056.17 | |
| one | 396 |
| 433.81 |
3 | 389 |
| 499.81 |
Tip |
---|
Moment values occurring in Ex loading are exactly the same with ideCAD Static Structural results. |
...
Note |
---|
Important Note: Complete Quadratic Combination (CQC or TKT) or square of the total of the |
...