TBDY 2018 7.6.1.1 (a) in Item 7.6.1.3 't Except as exceptions, rectangular and U, L and T as the curtains shearwalls of the body of the wall thickness times the height of 1/16 from and will be less than 250 mm, a condition .
You receive this warning because the curtain shearwall thickness is less than 250 mm and the special condition given in 7.6.1.3 is not met. If 7.6.1.3 is provided, the wall thickness can be 200 mm.
7.6.1.3 - In buildings whose structural system consists of walls, if both conditions given in Equation (7.14) are met, the wall thickness shall not be less than 1/20 and 200 mm of the height of the highest floor story in the building.
Σ A g / Σ A p ≥ 0.002 and V t / Σ A g ≤ 0.5 f ctd (7.14)
Solution:
Give the size of the curtain shearwall with the name and fold as at least 250 mm.
Choose
...
shearwall,
...
shearwalls.
Enter the properties.
In the general settings tab, increase the
...
shearwall width and click the OK button.
...
Alternatively, the conditions given in 7.6.1.3 can be met. Your Ag can be enlarged.
...
ΣAg = The sum of the cross-sectional areas of the structural system elements working as a curtain shearwall parallel to the earthquake direction considered at any floor.
ΣAp = Sum of plan areas of all floors stories of the building
Vt = Total earthquake load (base shear force) acting on the building according to TBDY 2018 Section 4
fctd = Design tensile strength of concrete
...
Related Topics
The shearwall thickness cannot be less than 1/30 of the shearwall length.
The upper floor shearwall is thicker than the lower floor shearwall
TBDY 7.11.5 in connection of elements with shearwall. conditions were not met.
In the shearwall group, the size ratio must meet (1/6) condition
There are shearwall groups that do not meet the capacity ratio.