The Complete Message:
Note |
---|
The raft floor stapling security foundation punching safety is not providedsatisfied. TBDY 7.11.7 |
...
The message stapling punching safety is not ensured is given for raft floors stories without beams together with the solid and element name.
...
7.11.10 - If the condition τ pd ≤ f ctd is not met and the plate thickness is not less than 250 mm, the punching strength of the slab can be increased by using reinforcement.
Possible solutions:
The thickness of the raft floor foundation can be increased.
Punching equipment can be used provided that the plate slab thickness is at least 250 mm.
Concrete class can be increased.
Column / curtain shear size size can be increased.
There are floor stroy gaps within the punching perimeter and can be canceled.
...