How does ideCAD control one-way slab design limits according to ACI 318-19?
...
Tip |
---|
|
...
Info |
---|
|
...
Symbols
h= overall thickness, height, or depth of member, in.
l= span length of beam or one-way slab; clear projection of cantilever, in.
fy = specified yield strength for nonprestressed reinforcement, psi
...
The minimum slab thickness is controlled automatically according to Table 7.3.1.1. If calculated deflection limits of 7.3.2 are satisfied, the minimum slab thickness condition does is not controlled.
Support Condition | Minimum slab thickness, h |
---|---|
Simply supported | l/20 |
One end continuous | l/24 |
Both ends continuous | l/28 |
Cantilever | l/10 |
For fy other than 60,000 psi, the expressions in Table 7.3.1.1 is are multiplied by (0.4 + fy/100,000).
...
For nonprestressed slabs not satisfying 7.3.1, immediate and time-dependent deflection is calculated according to 24.2 and is does not exceed the limits in 24.2.2.
...
It’s automatically designed according to Strength Reduction Factors per ACI 318-19 with ideCAD.
...