9.3.4.1 - The following three conditions shall be met at the beam-column connections of highly ductile moment-resisting steel frames.

The connection shall be capable of accommodating a story drift angle of at least 0.04 rad.

(a) The connection shall be capable of providing at least 0.04 radian relative story drift angle (relative story displacement/story height). For this purpose, connection details that have been validated by experimental and/or analytical methods will be used. Various examples of bolted and welded connection details and their prequalification limits that have been proven to be valid are given in  Annex 9B.

(b) The Annex 9B defines how to compute required moment resistance at the column face Muc by using the expected plastic bending moment of the beam Mp and possible plastic hinge location from the beam end Lh using Eq. (9.11).

In determining the required bending moment strength, the contribution of the additional bending moment from gravity loads for the part of the beam between the plastic hinge and the column face must be taken into account.

(c) To determine the Vu, the shear flow mechanism is taken into account to determine shear forces due to gravity resulting from (1.2 G +0.5 Q +0.2 S) combination and shear due to formation of the plastic hinge at beam end or column face by Eq. (9.12).

9.3.4.2 - In the beam-column connection detail, the required shear strength Vup of the panel zone limited by the column and beam flanges (Figure 9.3) shall be computed by Eq. (9.13) based on the column shear force resulting from the effect of possible plastic moments of the beams connected to the column.    

(a) The panel zone is dimensioned to have sufficient shear strength. For this, the design shear strength of the panel zone will be determined by ϕv = 1.0 (YDKT), taking into account the yield limit state in shear effect. If this condition is not fulfilled, the panel zone will be strengthened by adding continuity plates or stiffeners in the diagonal direction.

(b) The smallest thickness of the column doubler plates and if used each of the continuity plates, shall meet the condition tminu / 180 (Figure 9.4). In cases where this condition is not fulfilled, the continuity plates and the column doubler plate will be welded to each other so that they work together and it will be checked that the sum of plate thicknesses meets the condition ∑ tu / 180.

(c) If doubler plates are used in the panel zone, full penetration groove weld or fillet weld shall be used to connect these plates to the column flanges (Figure 9.4). These welds will be dimensioned by taking into account the shear force borne by the reinforcement plate.

9.3.4.3 - In beam-column joint details that transfer momentum , continuity plates will be placed on both sides of the column body at the level of beam heads, and it will be ensured that the tensile and pressure forces on the beam heads are transferred to the column (and to the neighboring beam in bilateral beam-column joints) (Figure 9.3) .

(a) The thickness of the continuity plates shall not be less than the head thickness of the joining beam in one-sided beam joints, and in the case of beam joining to the column from both sides, the thickness of the headers of the joining beams shall not be less.

(b)    Full penetration butt welding will be used for the connection of the continuity plates to the column bodies and heads. Corner welding can also be used for the connection of the continuity plate to the column body. However, this weld should be of the length and thickness to transfer a force equal to the shear capacity of the continuity plate in its own plane to the column body.

(c) Column head thickness

Continuity plate may not be required if both conditions meet.

9.3.4.4 - In dimensioning the beam-column connection detail, the calculation principles given in Annex 9B will be used.

9.3.4.5 - Capacity conserved regions as well, 9.2.9 shall also comply with the conditions. It is not permitted to use headed slip elements within these zones. 