Requires double reinforcement

Requires double reinforcement

This message is created with the element name with its story at the beginning of the report.

For example Story 1, D4, Requires double reinforcement.

1. The finite element mesh system may not have been created correctly

Possible solutions:

  • The connections of the boundy elements of the slabs may not be connected to each other correctly. Check the slab boundry to solve the mesh problem.

  • Check if the finite element meshing are created correctly which the problem may be solved by reducing widths of finite elements of the slabs and raft foundations that defined in the project

2. Reinforcement must be added to areas with insufficient reinforcement.

Possible solution:

In the analysis settings, if "Consider in plane forces for slab reinforcement design" option is selected, rebars may be required in the upper and lower regions of the slab section at the same time. Setting the rebar type of the calculation line of the slabs to “Upper + under straight reinforcement” may solve the problem.