Sample Slab Design
Sample Slab Design
As an example, the punching calculation of the 11th-story slab S03 without internal column beams will be made. In addition, it will be shown that the seismic forces are transferred safely from the slab to the shearwall in the strong direction of the 10th-story P45 shearwall.
Punching Checks
In slab-column combinations in non-beamed slab systems, the value obtained by multiplying the total bending moment transferred to the column in the direction taken into account at the story level under the effects of earthquakes with vertical loads, D, together with the vertical loads according to TBDY 7.11.8, with the bending reinforcement value of 1-γf the value obtained by multiplying by the coefficient is assumed to be tr